FEATURES
• Long detection range to carbonaceous fires.
• Unequaled false alarm rejection.
• Responds to a fire in the presence of modulated
blackbody radiation (i.e. heaters, ovens, turbines)
without false alarm.
• Heated optics for increased resistance to moisture
and ice.
• Factory sealed device eliminates need for explosion-
proof conduit seal.
• Automatic and manual optical integrity (o
i)
test.
• Easily replaceable o
i
plate.
• Tricolor LED indicates normal operation, fire and fault
conditions.
• Multiple mounting options include mounting directly
onto most junction boxes using a simple adapter, or
the use of a swivel union or swivel mount available
from Det-Tronics.
• Operates under adverse weather conditions and in
dirty environments.
• Hazardous location capabilities:
- Explosion-proof/flame-proof detector housing.
CSA, FM and CENELEC Certified.
- Models available with CENELEC Certified EEx d e.
• Class A wiring per NFPA-72.
• 5 year warranty.
SPECIFICATIONS
OPERATING VOLTAGE—
24 volts dc nominal (18 vdc minimum, 32 vdc
maximum).
POWER CONSUMPTION—
7.5 watts at 24 volts dc nominal; 9.0 watts at 32 volts dc
maximum.
POWER UP TIME—
Fault indication clears after 0.5 second; device is ready
to indicate an alarm condition after 30 seconds.
TEMPERATURE RANGE—
Operating: –40°F to +167°F (–40°C to +75°C).
Storage: –67°F to +185°F (–55°C to +85°C).
Hazardous location ratings from -55°C to +125°C
available on extended temperature model.
HUMIDITY RANGE—
0 to 95% relative humidity, can withstand 100%
condensing humidity for short periods of time.
DIMENSIONS—
See Figures 11A and 11B.